Analyzing the operation of a hybrid photovoltaic-diesel-generator-grid hybrid microsystem—Case study
The scientific objective of this study is to demonstrate how a hybrid photovoltaic-grid-generator microsystem responds under transient regime to varying loads and grid disconnection/reconnection. The object of the research was realized by acquiring the electrical magnitudes from the three PV systems (25 kW, 40 kW, and 60 kW) connected to the grid and the consumer (on-grid), during the technological process where the load fluctuated uncontrollably. Similar recordings were also made for the transient regime caused by the grid disconnection, diesel generator activation (450 kVA), its synchronization with PV systems, power supply to receivers, and grid voltage restoration after diesel generator shutdown. Analysis of the data focused on power supply continuity, voltage stability, and frequency variations. Findings indicated that on-grid photovoltaic systems had a 7.9% maximum voltage deviation from the standard value (230 V) and a frequency variation within ±1%. In the transient period caused by the grid disconnection and reconnection, a brief period with supply interruption was noted. This study contributes to the understanding of hybrid system behavior during transient regimes.